Printer friendly version of this page. Find a Distributor near you.
5205-Ethernet-PDPS

BACNet/IP Client to PROFIBUS DP Slave

5205-BACNET-PDPS

Disponibilidade Limitada: Produto em estoque limitado. More Info

The ProLinx BACnet/IP Client to PROFIBUS DPV0 Slave Gateway creates a powerful connection between a PROFIBUS Master and BACnet/IP devices. This stand-alone DIN-rail mounted protocol gateway provides a PROFIBUS Slave port and a single Ethernet port.

The ProLinx BACnet/IP Client (Building Automation and Control networking) Edition 1 protocol version is designed specifically to meet the communication needs of building automation and control systems for applications such as heating, ventilating, and air-conditioning control, lighting control, access control, and fire detection systems with limited BACnet/IP command support.

Funcionalidades e Beneficios

  • Standard protocol for Building Automation and Control limited to Analog and Digital I/O commands
  • Adds BACnet/IP device monitoring and control to a PROFIBUS DP network
  • Communicate with Building Automation controllers, HVAC, Fire and Safety equipment.
  • Support for Trane Building Control Unit (BCU)

Aplicações

  • Standard protocol for Building Automation and Control limited to Analog and Digital I/O commands
  • Adds BACnet/IP device monitoring and control to a PROFIBUS DP network
  • Communicate with Building Automation controllers, HVAC, Fire and Safety equipment.
  • Support for Trane Building Control Unit (BCU)

Especificações

Internal Database

The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.

The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.

Application Data Area

The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.

Status Data Area

This area is used to store error codes, counters, and port status information for each port.

Configuration Data Area

This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.

Hardware

BACnet/IP and
Configuration
Ethernet Port

10 Base-T half duplex RJ45 Connector
Link and Activity LED indicators
Electrical Isolation 1500 V RMS at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

Downloads

ProSoft Configurationo Builder (PCB)
BACNET PDPS Datasheet 100,07 kB Última modificação 11/05/2010
BACNET Protocol Manual 742,83 kB Última modificação 16/02/2012
PDPS Driver Manual 684,88 kB Última modificação 10/12/2009

Protocolos

BACNET Protocol Specification


Protocol Specifications

The BACnet/IP (Building Automation and Control networking) protocol is designed specifically to meet the communication needs of building automation and control systems for applications such as heating, ventilating, and air-conditioning control, lighting control, access control, and fire detection systems. The ProLinx BACNET driver implements a subset of the BACnet/IP protocol.

BACnet/IP Client Specifications

The module controls the read/write data transfer between the gateway and other BACnet/IP devices.

BACnet/IP Client Specifications

General

One client

Command List

Support for 100 commands, each configurable for command, IP address, register to/from addressing and word/bit count.

Service Port

1 to 65535

Function Code

12, 14, 15 and 16 (Read/Write Single & Multiple)

Data Type

0, 1, 3 and 4 (BO, BI, AO & AI)

Point Count

1 to 25


PDPS Protocol Specification


The PROFIBUS DP Slave protocol driver supports the PROFIBUS V0 Slave implementation, providing powerful data transfer capability between the ProLinx module and Siemens PLCs or other hosts. User configurable data mapping and DP port operation make the interface an easy to use and powerful data transfer tool.


Protocol Specifications

The PROFIBUS DP Slave driver gives access to the ProLinx unit's internal database via 244 bytes of Input data and 244 bytes of Output data (maximum 400 bytes total). These Input and Output data blocks are mapped by the user within the ProLinx module's data memory allowing the user maximum flexibility and data transfer with other protocols.

General Parameters

GSD File

PRLX05A5.GSD

Downloadable from ProSoft Technology web site

PROFIBUS Specifications

Communication parameters

Baud Rate: 9.6 kbps to 12 Mbps

Supported I/O length

244 bytes Input data

244 bytes Output data

400 bytes total

Supported PROFIBUS DP features

PROFIBUS V0 Slave using Siemens SPC3 chipset

Freeze Mode

Sync Mode

Auto Baud Setting

Configurable Parameters

PROFIBUS Node Address: 1 to 125

Data byte swapping

Action on loss of PROFIBUS connection

Comm Fail Timeout Multiplier

Status Data location in Internal Database


Certificações

CB Safety 35,78 kB Última modificação 27/08/2012
CE Mark 92,31 kB Última modificação 22/02/2013
Russian GOST-R 7,07 MB Última modificação 22/02/2013
GOST-R Declaration of Conformity 6,68 MB Última modificação 22/02/2013
UL/cUL; Class 1, Div 2 1,08 MB Última modificação 02/07/2013
UL/cUL; Class 1, Div 2 (Canada) 1,10 MB Última modificação 02/07/2013