Printer friendly version of this page. Find a Distributor near you.
5205-Ethernet-PDPS

IEC 60870-5-104 Server to PROFIBUS DP Slave Gateway

5205-104S-PDPS

The IEC 60870-5-104 Server to PROFIBUS DP Slave Gateway creates a powerful connection between devices on an IEC 104 network and PROFIBUS DP Master devices. This stand-alone DIN-rail mounted gateway provides one PROFIBUS DP-V0 Slave DB9F port and one IEC 104 Server Ethernet port.

The 104S gateway accepts and responds to commands from a network-connected Client (Master) and can also autonomously generate unsolicited messages for cyclic or event-driven data transmission. Firmware versions 3.00 and later support a wider range of IEC 60870-5-104 Edition 2 data types and Causes of Transmission than previously offered.

The PROFIBUS Slave protocol supports the PROFIBUS DP-V0 implementation, providing powerful data transfer capability between the ProLinx gateway and a PROFIBUS DP Master. With relatively few options to adjust, the PROFIBUS DP Slave configuration is quick, simple, and easily accomplished using the provided ProSoft Configuration Builder software.

Funcionalidades e Beneficios

Powerful network integration

  • Move data between dissimilar networks using two communication protocols on one gateway
  • Protocols share access to a common memory database to exchange data between networks
  • View diagnostic data for both networks from a single configuration/debug port

IEC 60870-5-104 Server protocol Interface

  • Adds an IEC 60870-5-104 Server (Slave) Input and Output link to a PROFIBUS DP network
  • IEC 60870-5-104, Edition 2 Data Types and extended Cause of Transmission Support
  • Advanced Event Buffer control parameters allow better data bandwidth utilization

PROFIBUS DP-V0 Slave protocol interface

  • Adds PROFIBUS DP Slave device monitoring and control to a IEC 60870-5-104 network
  • Easy configuration - GSD file provided
  • PROFIBUS Slave status may be stored in gateway database and retrieval by either protocol

ProSoft Configuration Builder software included

  • Graphical drag-and-drop configuration tool for simple module configuration
  • Easy-to-use diagnostics window with menu-driven hardware and protocol diagnostics
  • View module database contents through serial connection to a desktop PC

Backed by ProSoft Technology

  • 20-year history of delivering high-quality, reliable solutions designed with you in mind
  • Free, unlimited, worldwide Technical Support by phone for pre-sale, set-up, or troubleshooting support helps you get going sooner and stay running longer
  • Three-Year Warranty ensures reliability and protects against equipment failures

Especificações

Internal Database

The ProLinx module contains an internal database that consists of areas for application data, status information, and configuration information.

The internal database is shared between all ports on the module and is used as a conduit to pass information from a device on one network to one or more devices on another network.

Application Data Area

The data area is used to store and retrieve data by the protocol drivers and for data exchange between protocols. The database is used as a source for write commands to remote devices and holds data collected from the remote devices. Commands defined in the configuration file (stored in the configuration data area) control how the data is to be handled in the database.

Status Data Area

This area is used to store error codes, counters, and port status information for each port.

Configuration Data Area

This area contains module configuration information such as port configuration, network information, and command configuration. This configuration file is downloaded to, or uploaded from, this area.

 

104S Protocol Specification

Operating in the Server mode, the protocol driver accepts commands from one or more clients to read/write data stored in the module's internal registers.

The 104S module acts as an input/output module between the IEC 60870-5-104 Ethernet network and many of the other serial and network protocols, as well as several proprietary interfaces.

General specifications include:

 

  • User-definable module memory usage
  • Protocol implementation conforms to the IEC 60870-5-104 specification with fully configurable parameters
  • SNTP (Simple Network Time Protocol) timestamping for detailed logging of data transactions

 

The 104S module accepts commands from an attached master unit on the network and generates unsolicited messages. These last sets of messages are either spontaneous or cyclic. Data transferred to the host is derived from the module's internal database. The remote master device can control data in the database and hence the devices connected using the other protocol in the module using standard control messages supported in the protocol. The remote master device uses the fully-configured databases in the module to control outputs and monitor inputs.

IEC 60870-5-104 Server

Configurable Parameters

Override StartDT 
Clear queue on close
t1 timeout set value 
t2 timeout set value
t3 timeout set value
k (maximum queue)
w (latest ack threshold)
Time DB Offset 

 

PDPS Protocol Specification

The PROFIBUS DP Slave driver gives access to the ProLinx unit's internal database via 244 bytes of Input data and 244 bytes of Output data (maximum 400 bytes total). These Input and Output data blocks are mapped by the user within the ProLinx module's data memory allowing the user maximum flexibility and data transfer with other protocols.

General Parameters

GSD File

PRLX05A5.GSD

Downloadable from ProSoft Technology web site

PROFIBUS Specifications

Communication parameters

Baud Rate: 9.6 kbps to 12 Mbps

Supported I/O length

244 bytes Input data

244 bytes Output data

400 bytes total

Supported PROFIBUS DP features

PROFIBUS V0 Slave using Siemens SPC3 chipset

Freeze Mode

Sync Mode

Auto Baud Setting

Configurable Parameters

PROFIBUS Node Address: 1 to 125

Data byte swapping

Action on loss of PROFIBUS connection

Comm Fail Timeout Multiplier

Status Data location in Internal Database

Hardware

Specification

Description

Power Supply

24 VDC nominal
18 to 32 VDC allowed
Positive, Negative, GND Terminals
2.5 mm screwdriver blade

Current Load

500 mA max @ 32 VDC max

Operating Temperature

-4° F to 122° F (-20° C to 50° C)

Storage Temperature

-40° F to 185° F (-40° C to 85° C)

Relative Humidity

5% to 95% (with no condensation )

Dimensions

Standard:
 5.20 in H x 2.07 in W x 4.52 in D (13.2 cm x 5.25 cm x 11.48 cm)
Extended:
 5.20 in H x 2.73 in W x 4.52 in D
(13.2 cm x 6.934 cm x 11.48 cm)

LED Indicators

Power and Module Status
Application Status
Serial Port Activity
Serial Port Error Status

Configuration Serial Port

DB-9M RS-232 only
No hardware handshaking

Ethernet Port (Ethernet modules only)

10Base-T half duplex RJ45 Connector
Link and Activity LED indicators
Electrical Isolation 1500 V RMS at 50 Hz to 60 Hz for 60 s, applied as specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration

Application Ports

Modbus Plus Connector
Two DB9 Female Standard Modbus Plus connectors

Serial Port Isolation

2500 V RMS port signal isolation per UL 1577
3000 VDC min. port to ground and port to logic power isolation

Shipped with Each Unit

Mini-DIN to DB-9M serial cables 
4 ft RS-232 configuration cable
2.5mm screwdriver
CD (docs and Configuration utility)
RS-422/485 DB-9 to Screw Terminal Adaptor (1 or 4, depending on ports)

Certificações

Ex Certificate (ATEX Directive) 114,27 kB Última modificação 11/11/2013
CB Safety 35,78 kB Última modificação 27/08/2012
CE Mark 92,31 kB Última modificação 22/02/2013
Russian GOST-R 7,07 MB Última modificação 22/02/2013
GOST-R Declaration of Conformity 6,68 MB Última modificação 22/02/2013
Korean KC Registration 851,60 kB Última modificação 22/02/2013
UL/cUL; Class 1, Div 2 1,08 MB Última modificação 02/07/2013
UL/cUL; Class 1, Div 2 (Canada) 1,10 MB Última modificação 02/07/2013